Data Centre Cabling Warnings from Siemon

by david.nunes

November 2010 – Global infrastructure expert Siemon has today launched two warnings: 1) Category 6 may well fail to deliver 10 Gb/s in data centre. 2) Beware of using non-Standards compliant 26AWG conductor cabling.  To ensure 10GBASE-T capability, Siemon recommends standards compliant category 6A or higher for data centre environments.

Siemon’s warnings come on the heels of ISO/IEC, TIA and other telecommunications standards organisations giving clear messages that the minimum grade of cabling to be deployed in the data centre is category 6A.  ISO/IEC 247643 states that main distribution cabling systems supporting data centres shall be designed to provide a minimum of class EA (equivalent to TIA category 6A) channel performance.  The working draft of ANSI/TIA-942-A2 explicitly states that category 6A is the recommended grade of horizontal and backbone cabling to install in new data centres.

This alert from Siemon is likely to concern a large number of data centre sites that have already adopted category 6:  Industry market research firm IDC recently reported that one million 10 Gigabit Ethernet ports were shipped during the second quarter of 2010 and a proportion of these switches are highly likely to have been deployed in the data centre.  As 10GBASE-T network equipment becomes increasingly available, data centre decisions makers will want to take advantage of the cost savings, convenience and flexibility provided by deploying 10 Gb/s technology over twisted-pair copper cabling.  Whilst previously installed legacy category 6 systems may provide limited support of 10GBASE-T in some environments, category 6 cabling is not recommended for new data centres and smaller 26AWG cabling is not recognised by the Standards.

Moreover, legacy category 6 installations for 10GBASE-T are significantly distance limited.  According to Standards, category 6 channels of less that 37 metres (121ft) in length should support the 10BASE-T application and channels between 37 metres and 55 metres (180 ft) may or may not support the application, depending upon the alien crosstalk environment and mitigation steps.  However, Siemon points out that supporting 10GBASE-T over installed legacy category 6 requires alien crosstalk field tests on every channel, which can be time-consuming and not fully conclusive.

Compounding the concern for category 6 cabling, Siemon points out that there are no applications under development for this standard.  Both TIA and ISO state that the cabling systems specified in their standards are intended to have a useful life in excess of 10 years.   Since the category 6 and class E cabling standards were published in 2002, these systems are already beyond the halfway point of their targeted lifecycle.    Furthermore, application development groups such as IEEE 802.3 or ATM are not investigating the development of new Ethernet or other data transmission solutions for deployment over category 6 cabling.

Adding to the justification for the category 6 data centre warning, Siemon concludes that, as category 6 UTP or 26AWG cables cannot support a full 100 metre 10GBASE-T channel, it limits design flexibility.  The standard cannot support power-saving short reach mode (data centre mode) and these cables, having reduced diameter conductors, cannot dissipate heat as well as category 6A or higher systems.   These factors add to the reasons to specify category 6A or higher grade in the data centre, says Siemon.

Photos to accompany this release are available on request from: direland@turtleconsulting.com

 

About Siemon

Established in 1903, Siemon is an industry leader specialising in the manufacture and innovation of high quality, high-performance copper and optical fibre network cabling solutions. With offices and partners throughout the world, Siemon offers a global service and has a reputation for delivering market leading performance with systems that maximise efficiency and return on investment.

Siemon’s products include the most comprehensive suite of copper available, in both unshielded and shielded twisted-pair, for category 5e, category 6 (Class E), category 6A (Class EA) and category 7/7A (Class F/FA) standards performance.  The company’s optical fibre range includes both multimode and singlemode cabling systems.  In addition to cabling systems, the company has developed specific and specialised products for network provision in both enterprise and hosted data centre environments, often partnering with other global industry leaders in delivery of complete solutions for these markets.  With over 400 patents specific to structured cabling, Siemon Labs invests heavily in R&D and development of industry standards, underlining the company’s long-term commitment to its customers and the industry.

www.siemon.com/uk

Follow Siemon on Twitter: http://twitter.com/siemoncabling

Join Siemon on Facebook: http://www.siemon.com/go/facebook

Related Articles

This website uses cookies to improve your experience. We'll assume you're ok with this, but you can opt-out if you wish. Accept Read More